Fantech
Heritage Ultra Series – HUD564
Download CatalogueAutocadPrint Friendly Version
Heritage Ultra Series - HUD564 - Fan

Performance Curve - HUD564

Performance Curve for Heritage Ultra Series HUD564

Description

The Heritage Ultra Series of vertical exhaust roof units has been designed for use in ducted exhaust applications. It features a high performance Mixed-Flow fan and removable windband which makes cleaning and maintenance easy.

There are 9 sizes in the series extending from 250 to 630mm diameter.

Features
  • Durable galvanised steel construction.
  • Designed to handle clean air, grease laden air, toxic and noxious gases.
  • Motor is mounted out of the airstream.
  • Special finishes, such as epoxy coating can be supplied.
  • Available in a range of speeds to suit specific applications.
  • Windband can be easily removed to allow easy access for cleaning and maintenance.
  • Can be mounted at angles up to 15°.
Construction

Cowls are of galvanised steel and can be coated as an optional extra.
Impellers are Mixed-Flow design.
Windband is fitted with quick-release toggle clamps to facilitate cleaning and maintenance.
Stainless steel construction is an optional extra.

Motors

Type - standard TEFC squirrel cage induction motors.
Electricity supply - three-phase to suit a wide range of voltages and frequencies.
Bearings - sealed-for-life, ball.
Speed-controllable using variable speed drives.
Multi-speed motors can be supplied.

Internal Thermal Protection

Thermistors can be fitted on request

Testing

Air flow tests based on ISO 5801
Noise tests based on ISO 13347-3

Suggested Specification

The roof ventilators shall be of the Heritage Ultra vertical exhaust series as designed and manufactured by Fantech Pty. Ltd and be of the model numbers shown on the schedule/drawing.

The cowl shall be of galvanised steel unless specified otherwise. Impellers shall be Mixed-Flow design and driven by standard TEFC motors unless specified otherwise.

The windband shall incorporate quick-release toggle clamps to provide easy access for cleaning and maintenance.

All models shall be fully tested as a complete assembled unit to ISO5801: 2007 for air flow. Noise tests shall be based on ISO13347-3

Technical Data - HUD564

Speed [rps] Avg. dBA @ 3m kWatts (Input) Amps Max.°C Approx. Weight [kg]
25 3 6.25 40 97

Sound Data

Type 63 125 250 500 1K 2K 4K 8K
Inlet 78 83 81 79 77 71 66 67
Outlet 81 88 86 86 85 77 72 70

Dimensions

Dimension Drawing for Heritage Ultra Series HUD564
A B C D E F
710 810 60 1160 665 965

*All dimensions in mm, unless otherwise stated

Wiring Diagram

Wiring Diagram for Heritage Ultra Series HUD564

Diagram shown is for single-speed only.
For 2-speed and special motors, contact Fantech for details.

Ancillaries

CBD-E - Backdraft Shutters
CBD-E
Backdraft Shutters
EP-HER63-71 - Epoxy Coating
EP-HER63-71
Epoxy Coating