Gamma Ultra Supply – GUD568S
                                    
                                 
                                
                                
                                
                                    
                                    
                                    
                                    
                                    
                                    
                                        Performance Curve - GUD568S
                                        
                                     
                                    
                                 
                                
                                
                                
                                    Description
                                    
The Gamma Supply Ultra Series of mixed-flow roof units have
been designed for use in free outlet and ducted installations.
These compact and low profile units are ideal for supplying fresh
air to an air handling unit or to an air conditioning system in
commercial buildings. 
They are available in 3 sizes extending from 450 to 560mm
diameter
                                 
                                
                                
                                
                                
                                    
                                    Features
                                    - Robust, lightweight construction.
-  Choice of speeds available.
-  Ideal for ducted installations.
-  High performance mixed-flow impellers fitted.
-  Can be mounted at angles up to 30°.
-  Most 3-phase motors are 2-speed star/delta design as
- standard.
-  Speed-controllable using electronic or auto-transformer controllers.
 
                                
                                
                                
                                
                                    
                                    
                                        Construction
                                        Cowls are of UV-stabilised plastic.
Steel components have a corrosion resistant finish.
Impellers are mixed-flow design and are of high performance
composite material.
Bird-mesh guards are fitted as standard.
Shutters cannot be fitted.
                                     
                                    
                                    
                                        Motors
                                        Type - external rotor, squirrel cage induction motor.  
Electricity supply - 230V, single and 415V, three-phase, 50Hz  Bearings - sealed-for-life, ball.
Speed-controllable using electronic or auto-transformer  controllers.  
Most three-phase units are fitted with 2-speed star/delta design  motors.
                                     
                                    
                                    
                                        Internal Thermal Protection
                                        Thermal protection is supplied as standard on all motors.
                                     
                                    
                                    
                                        Testing
                                        Air flow tests to ISO 5801: 2007.
Noise tests to ISO 13347-3. 
                                     
                                    
                                 
                                
                                
                                
                                    
                                    
                                        Suggested Specification
                                        The roof ventilators shall be of the Gamma Supply Ultra Series  supply air type as designed and manufactured by Fantech Pty Ltd.
Impellers shall be made from high performance injection moulded  composite material. They shall be mixed-flow design and driven  by speed-controllable external rotor motors with integral thermal  overload protection.  
The cowls shall be manufactured from UV-stabilised plastic. Steel  components to be corrosion protected.  
All performance data shall be for a complete assembled unit  based on ISO5801 for air flow and ISO 13347-3 for noise
 
                                    
| Speed [rps] | Avg. dBA @ 3m | kWatts (Input) | Amps | Max.°C | Approx. Weight [kg] | 
| 13 |  | 0.62 | 1.1 | 60 | 53 | 
  
| Type | 63 | 125 | 250 | 500 | 1K | 2K | 4K | 8K | 
| Inlet | 67 | 67 | 64 | 61 | 66 | 62 | 56 | 50 | 
| Outlet | 54 | 65 | 68 | 68 | 69 | 64 | 58 | 46 | 
  
Dimensions
| A | B | C | D | E | 
| 805 | 905 | 670 | 1180 | 95 | 
*All dimensions in mm, unless otherwise stated
 
 
Wiring Diagram
 
Diagram shown is for single-speed only. 
For 2-speed and special motors, contact Fantech for details.