Gamma Ultra - Vertical – GUD354V
                                    
                                 
                                
                                
                                
                                    
                                    
                                    
                                    
                                    
                                    
                                        Performance Curve - GUD354V
                                        
                                     
                                    
                                 
                                
                                
                                
                                    
Description
                                    The Gamma Ultra Series of Mixed-Flow roof units has been designed for use in commercial ducted exhaust applications. These compact and low profile units are fitted with birdmesh to prevent the entry of birds and vermin into the ducting or building. They are available in 9 sizes, extending from 250 to 630mm diameter.
                                
                                
                                
                                
                                
                                    
                                    Features
                                    -  Robust, lightweight construction.
-  Choice of speeds available.
- Compact, low profile design.
-   Designed for down flow or vertical exhaust applications.
-   Shutters are an optional extra for single fan units. The pressure loss across the shutter has to be added to the system pressure before making selections.
-  Can be mounted at angle up to 30°.
-   Most 3-phase motors are 2-speed star/delta design.
 
                                
                                
                                
                                
                                    
                                    
                                        Construction
                                        Cowls are UV-stabilised plastic.
Impellers are Mixed-Flow design and made from high performance injection moulded composite material.
Steel components have a corrosion resistant finish. 
Bird-mesh guards are fitted as standard to both downflow and vertical exhaust models.
                                     
                                    
                                    
                                        Motors
                                        Type - external rotor, squirrel cage induction motor 
 
Electricity supply - 230V, single and 415V, three-phase, 50Hz 
Bearings - sealed-for-life, ball 
Speed-controllable using electronic or auto-transformer controllers  
Most three-phase units are fitted with 2-speed star/delta design motors
                                     
                                    
                                    
                                        Internal Thermal Protection
                                        Thermal protection is supplied as standard on all motors
                                     
                                    
                                    
                                        Testing
                                        Air flow tests based on ISO5801
Noise tests based on ISO13347-3
                                     
                                    
                                 
                                
                                
                                
                                    
                                    
                                        Suggested Specification
                                        The Gamma Ultra Series roof ventilators shall be of the vertical exhaust type as designed and manufactured by Fantech Pty. Ltd. 
Impellers shall be made from high performance injection moulded composite material. They shall be Mixed-Flow design and driven by speed-controllable external rotor motors with integral thermal overload protection. 
The windband shall be of the vertical exhaust design and formed from plastic. Steel components shall be corrosion protected. 
All performance data shall be for a complete assembled unit to ISO5801 for air flow and ISO13347-3 for noise.
                                     
                                    
| Speed [rps] | Avg. dBA @ 3m | kWatts (Input) | Amps | Max.°C | Approx. Weight [kg] | 
| 23 | 46 | 0.33 | 0.68 | 60 | 15 | 
  
| Type | 63 | 125 | 250 | 500 | 1K | 2K | 4K | 8K | 
| Inlet | 69 | 69 | 68 | 64 | 62 | 60 | 55 | 47 | 
| Outlet | 71 | 73 | 72 | 70 | 67 | 64 | 58 | 50 | 
  
Dimensions
| A | B | C | D | E | F | G | 
| 400 | 500 | 75 | 640 | 670 | 410 | 417 | 
*All dimensions in mm, unless otherwise stated
 
 
Wiring Diagram
 
Diagram shown is for single-speed only. 