JetVent Car Park EC - LH – JIU-CPCEC-LH
Location Designation
Project Notes
JetVent Car Park EC - LH
Description
The JetVent LH (Low Profile) EC model fan is designed to clear harmful pollutants from enclosed and semi-enclosed spaces. It features a compact overall size and a very narrow height, which may enable the car park’s floor to ceiling dimensions to be reduced.

The Low Profile JetVent comes in three phase model with a centrifugal aluminium impeller, has been developed for higher air flows and has a pre-set speed thrust rating of 23 Newtons.

Features
  • The LH JetVent is a three phase EC model
  • An energy efficient ventilation system that provides the ventilation rate according to the CO or NOx pollutant levels in the space.
  • Available with a factory fitted and fully integrated smoke detection kit mounted to the side of the JetVent fan.
  • Additional decentralised smoke detectors can be connected to the JetVent system based on car park layout.
  • Utilises Aviator controls to digitally connect JetVent fans, Supply & Exhaust fans, Sensors and the BMS together.
  • Aviator controls with propriety ComLink system provides a simple control wiring scheme with easy installation, fast commissioning and a high level of system monitoring.
  • EC motor features reverse polarity protection, locked rotor protection and soft starting.
  • EC motor technology eliminates the need for external VSDs, current overloads and motor phase protection.
Construction
Low-profile galvanised steel housing with aerodynamically designed internal flow elements.
Motor
Type - Electronically commutated (EC) Motor.
Electricity supply - 380V-480V, three-phase, 50/60 Hz.
Bearings - sealed-for-life ball.
Integrated EC-Controller providing infinite speed control.
Integrated EC speed control over analogue 0-10V or 4-20mA,
PWM or MODBUS High Level Interface over RS485.
Internal Protection
Integral thermal overload protection is supplied as standard.
Testing
Thrust-air performance based on tests to BS848 Part 10,1999
"Fans for general purpose - Performance testing of jet fans."
Noise data based on tests to BS848:Part 2,1985.
Special Note
In most cases Jet fans will be treated as a mechanical performance solution within the National Construction Code (NCC) (formally the BCA). Where required, a mechanical performance solution should comply with the AFAC Guideline 1.0 on Fire Safety for impulse (Jet) fans in Car Parks, and be approved by the appropriate authority. The mechanical performance solution should contain a pollutant analysis and detailed justification to demonstrate the jet fan system will not have a significant detrimental effect on the safe egress of occupants or operation of the sprinkler system.
Performance Curve for JetVent Car Park EC - LH JIU-CPCEC-LH

Technical Data - JIU-CPCEC-LH

Speed [rps] Avg. dBA @ 3m kWatts (Input) Amps Max.°C Approx. Weight [kg]
30 69 1.7 2.6 40 89

Sound Data

Type 63 125 250 500 1K 2K 4K 8K
Inlet 82 85 91 83 84 82 80 74
 
JetVent Car Park EC - LH – JIU-CPCEC-LH
Suggested Specification
The high velocity jet fans shall be of the low height JetVent JIU-CPCEC Series as designed and manufactured by Fantech Pty Ltd and be of the model numbers shown on the schedule/drawings. The impellers must be driven by EC external rotor motors with integrated EC-Controller and integral thermal overload protection. They shall be pre-configured to suit CO/NOx sensors and the required applications.

The housing shall be of galvanised steel with a light grey powder coated finish as standard. They shall incorporate mounting feet and aerodynamically designed internal flow elements

Performance data shall be based on tests to BS848:Part 10,1999 for thrust and ISO3744 or ISO13347-3 for noise.

 

Dimensions

Dimension Drawing for JetVent Car Park EC - LH JIU-CPCEC-LH
A B C D E F G H I
1745 322 906 68 25 13 973 605 675

*All dimensions in mm, unless otherwise stated

Contacts



OFFICES & AGENTS

Victoria
Fantech Pty. Ltd.
Tel:+61 (03) 9554-7845

New South Wales
Fantech Pty. Ltd.
Tel:+61 (02) 8811-0400

Uniair Distributors Pty. Ltd.
Tel:+61 (02) 4961-6088
Refrigeration and Air Supplies
Tel:+61 (02) 4226-5133

South Australia
Fantech Pty. Ltd.
Tel:+61 (08) 8294-0530

Queensland
Fantech Pty. Ltd.
Tel:+61 (07) 3299-9888
Capricorn Air Conditioning
Tel:+61 (07) 4775-5222

Northern Territory
Fantech Pty. Ltd.
Tel:+61 (08) 7918-5122

Western Australia
Systemaire Pty. Ltd.
Tel:+61 (08) 9209-4999

Tasmania
Major Air Pty. Ltd.
Tel:+61 (03) 62736455

ACT
Idealair Group Pty. Ltd.
Tel:+61 (02) 6280-5511

Auckland
Fantech (NZ) Ltd.
Tel:+64 (09) 444-6266

Christchurch
Fantech (NZ) Ltd.
Tel:+64 (03) 379-8622

Wellington
Fantech (NZ) Ltd.
Tel:+64 (04) 566-0532