    	 Description 
        
		    The Gamma Ultra Series of Mixed-Flow roof units has been designed for use in commercial ducted exhaust applications. These compact and low profile units are fitted with birdmesh to prevent the entry of birds and vermin into the ducting or building. They are available in 9 sizes, extending from 250 to 630mm diameter. 
            
                Features
                -  Robust, lightweight construction.
 
-  Choice of speeds available.
 
- Compact, low profile design.
 
-   Designed for down flow or vertical exhaust applications.
 
-   Shutters are an optional extra for single fan units. The pressure loss across the shutter has to be added to the system pressure before making selections.
 
-  Can be mounted at angle up to 30°.
 
-   Most 3-phase motors are 2-speed star/delta design.
 
  
           
        -  Robust, lightweight construction.
 
-  Choice of speeds available.
 
- Compact, low profile design.
 
-   Designed for down flow or vertical exhaust applications.
 
-   Shutters are an optional extra for single fan units. The pressure loss across the shutter has to be added to the system pressure before making selections.
 
-  Can be mounted at angle up to 30°.
 
-   Most 3-phase motors are 2-speed star/delta design.
 
  
                    
		    
                Construction 
                Cowls are UV-stabilised plastic. 
Impellers are Mixed-Flow design and made from high performance injection moulded composite material. 
Steel components have a corrosion resistant finish.  
Bird-mesh guards are fitted as standard to both downflow and vertical exhaust models.
 
            
                            
                Motor 
                Type - external rotor, squirrel cage induction motor   
Electricity supply - 230V, single and 415V, three-phase, 50Hz  
Bearings - sealed-for-life, ball  
Speed-controllable using electronic or auto-transformer controllers   
Most three-phase units are fitted with 2-speed star/delta design motors 
              
             
            
                Internal Protection 
                Thermal protection is supplied as standard on all motors
             
            
            
                Testing 
                Air flow tests based on ISO5801 
Noise tests based on ISO13347-3
             
            
            
                Special Note 
                 
            
            
                Special Features 
                
             
            
     | 
    
		
        
            
| Speed [rps] | 
Avg. dBA @ 3m | 
kWatts (Input) | 
Amps | 
Max.°C | 
Approx. Weight [kg] | 
 
| 15 | 
51 | 
0.54 | 
2.5 | 
60 | 
35 | 
 
   
 
| Type | 
63 | 
125 | 
250 | 
500 | 
1K | 
2K | 
4K | 
8K | 
 
| Inlet | 
72 | 
77 | 
70 | 
65 | 
66 | 
67 | 
59 | 
52 | 
 
| Outlet | 
77 | 
79 | 
76 | 
70 | 
72 | 
67 | 
61 | 
49 | 
 
   
 
         	
     |