Description
The ProVent Series of in-line mixed-flow fans have been specifically designed for ducted supply or exhaust air applications.
There are 6 models in the range matching standard duct sizes from 100 to 200mm diameter.
Features
- High performance mixed-flow Impeller.
- Models 150SW and 200SW include an external
mounted 2-speed switch.
- Models 150TSW and 200TSW include a 1-30 minute adjustable run-on timer and external mounted
2-speed switch.
- Fans can be removed for maintenance or repair without disturbing the duct system via specially designed
support brackets.
- Integrated mounting foot makes installation easier.
- All models include plug and lead for easy installation.
- Can be mounted in any position.
- High performance mixed-flow Impeller.
- Models 150SW and 200SW include an external
mounted 2-speed switch.
- Models 150TSW and 200TSW include a 1-30 minute adjustable run-on timer and external mounted
2-speed switch.
- Fans can be removed for maintenance or repair without disturbing the duct system via specially designed
support brackets.
- Integrated mounting foot makes installation easier.
- All models include plug and lead for easy installation.
- Can be mounted in any position.
Construction
The housings are of reinforced, injection moulded
polypropylene plastic. The mixed-flow impellers are of injection moulded plastic.
Motor
Type - 2-speed, squirrel cage, capacitor run.
Electricity supply - 230V, single-phase, 50Hz.
Class B insulation, IP44.
Bearings - sleeve for RIL-100 and RIL-125, ball for all other models.
Speed-controllable using VA type speed controller in high
speed setting only.
The RIL-150TSW and RIL-200TSW cannot be speed controlled.
Internal Protection
By fuse to size 125 and for all other models manual-reset thermal overload protection device in accordance with mandatory requirement for in-duct fans AS/NZS60335-2-80:2004
Testing
Air flow to ISO5801:Part1, 1997
Noise to BS848:Part 2, 1985
Meets requirements of AS/NZS60335-2-80:2004
Special Note
Special Features
|
Technical Data - RIL-200SW
Setting |
Speed [rps] |
Avg. dBA @ 3m |
kWatts (Input) |
Amps |
Max.°C |
Approx. Weight [kg] |
Lo |
33 |
42 |
0.1 |
0.45 |
60 |
4.9 |
Hi |
42 |
47 |
0.12 |
0.5 |
60 |
4.9 |
Setting |
Type |
63 |
125 |
250 |
500 |
1K |
2K |
4K |
8K |
Lo |
Inlet |
48 |
53 |
56 |
59 |
58 |
60 |
54 |
47 |
Lo |
Outlet |
67 |
57 |
56 |
59 |
63 |
62 |
57 |
49 |
Lo |
Breakout |
41 |
49 |
47 |
43 |
47 |
48 |
38 |
28 |
Hi |
Inlet |
53 |
58 |
61 |
64 |
64 |
65 |
59 |
52 |
Hi |
Outlet |
72 |
62 |
62 |
64 |
68 |
67 |
62 |
54 |
Hi |
Breakout |
46 |
54 |
52 |
49 |
52 |
53 |
43 |
33 |
|