    	 Description 
        
		    The Gamma Series of centrifugal roof units has been 
designed for use in commercial ducted exhaust applications. These compact and low profile units are fitted with birdmesh 
to prevent the entry of birds and vermin into the ducting 
or building. They are available in 12 sizes, extending from 
192 to 710mm diameter. 
            
                Features
                -  Robust, lightweight construction.
 
-  Choice of speeds available.
 
-  Compact, low profile design.
 
-  Designed for down flow exhaust applications.
 
-  Twin vertical discharge fan also available. Provides 100% standby capacity.
 
-  Shutters are standard on twin fan units and an optional extra for single fan units. The pressure loss across the shutter has to be added to the system pressure before making selections.
 
-  Can be mounted at angle up to 30°.
 
-  Most 3-phase motors are 2-speed star/delta design.
 
-  Supply air units can be supplied
 
  
           
        -  Robust, lightweight construction.
 
-  Choice of speeds available.
 
-  Compact, low profile design.
 
-  Designed for down flow exhaust applications.
 
-  Twin vertical discharge fan also available. Provides 100% standby capacity.
 
-  Shutters are standard on twin fan units and an optional extra for single fan units. The pressure loss across the shutter has to be added to the system pressure before making selections.
 
-  Can be mounted at angle up to 30°.
 
-  Most 3-phase motors are 2-speed star/delta design.
 
-  Supply air units can be supplied
 
  
                    
		    
                Construction 
                Cowls are UV-stabilised plastic. 
Impellers are backward-curved centrifugal design and can be plastic, steel or aluminium. 
Steel components have a corrosion resistant finish. 
Bird-mesh guards are fitted as standard to both downflow and vertical exhaust models. 
            
                            
                Motor 
                Type - external rotor, squirrel cage induction motor
 Electricity supply - 230V, single and 415V, three-phase, 50Hz
 Bearings - sealed-for-life, ball
 Speed-controllable using electronic or auto-transformer controllers (except CE316)
 Most three-phase units are fitted with 2-speed star/delta design motors
              
             
            
                Internal Protection 
                Thermal protection is supplied as standard on all motors.
             
            
            
                Testing 
                Air flow tests to ISO5801:2007
 Noise tests to BS848:Part 2, 1985
             
            
            
                Special Note 
                 
            
            
                Special Features 
                
             
            
     | 
    
		
        
            
| Speed [rps] | 
Avg. dBA @ 3m | 
kWatts (Input) | 
Amps | 
Max.°C | 
Approx. Weight [kg] | 
 
| 15 | 
46 | 
0.44 | 
1.2 | 
0 | 
38 | 
 
   
 
| Type | 
63 | 
125 | 
250 | 
500 | 
1K | 
2K | 
4K | 
8K | 
 
| Inlet | 
77 | 
76 | 
67 | 
64 | 
59 | 
57 | 
55 | 
51 | 
 
   
 
         	
     |